Products » Current Transducers » RPS51

- Four selectable scales
- Equalization and 90° shifting of the Rogowski coil signal
- 1 A RMS full scale output for instantaneous value
- Compact DIN rail enclosure
- 85 ... 265 VAC power supply
- Measuring devices, lab instrumentation
- Power monitoring & control systems
- Harmonics and transients monitoring
- DC ripple measurement
- Welding machine control
- High current measurement
Type: Auxiliary
Voltage range: 85 ... 265 V AC
Consumption: 10 VA, 20 VA max in overload
Safety: 300 V CAT III
Electrical characteristics
Input: 100 mV / kA @ 50 Hz (RMS values) MFC150/MFC140 Rogowski coil
AC output: 1 A RMS
Crest factor: 2
Selectable scales: 100 / 1 A
500 / 1 A
1000 / 1 A
5000 / 1 A
Bandwidth: 40 – 3200 Hz
Phase error: < 0.1° with 40 ... 150 Hz range
< 1° with 150 ... 1000 Hz range
< 2° with 1000 ... 3200 Hz range
Environmental conditions
Operating temperature: -25 ... +55°C
Storage temperature: -25 ... +70°C
Relative humidity: 0 ... 80%
Mechanical characteristics
Material: Plastic enclosure
Protection degree: IP20
Size: 115x100x23 mm
Weight: Approx. 117 g
Installation and use: Indoor
Standards compliance
Safety: EN / IEC 61010-1
EMC: EN / IEC 61326-1